Calibrating a Fisher™ 3582 Positioner - Beam Alignment
Fisher Valves & Instruments Fisher Valves & Instruments
28.6K subscribers
91,111 views
798

 Published On Jul 26, 2016

Learn about proper calibration and beam alignment procedures for the Fisher 3582 pneumatic positioner.

Steps include:
1. Turn the nozzle all the way in and then out four complete turns.
2. Set the input signal to the middle of its range.
3. Move the flapper assembly over the cam and adjust the flapper assembly screw to align the feedback arms.
4. Turn flapper assembly from direct 10 to reverse 10 to align arms using bellows pin and beam pivot pin.

Additional Resources:
– Fisher 3582 Instruction Manual: http://emr.sn/3YH7
– Fisher 3582 Product Bulletin: http://emr.sn/n9PF
– Fisher 3582 Product Webpage: http://emr.sn/Kn5W

Thanks for watching! Please like, share, and comment on our video and make sure to subscribe to the Fisher Valves & Instruments channel.

show more

Share/Embed